Thermodynamic study of wet cooling tower performance
- 1 May 2006
- journal article
- Published by Hindawi Limited in International Journal of Energy Research
- Vol. 30 (6), 411-426
- https://doi.org/10.1002/er.1158
Abstract
An analytical model was developed to describe thermodynamically the water evaporation process inside a counter-flow wet cooling tower, where the air stream is in direct contact with the failing water, based on the implementation of the energy and mass balance between air and water stream describing thus, the rate of change of air temperature, humidity ratio, water temperature and evaporated water mass along tower height. The reliability of model predictions was ensured by comparisons made with pertinent experimental data, which were obtained from the literature. The paper elaborated the effect of atmospheric conditions, water mass flow rate and water inlet temperature on the variation of the thermodynamic properties of moist air inside the cooling tower and on its thermal performance characteristics. The analysis of the theoretical results revealed that the thermal performance of the cooling tower is sensitive to the degree of saturation of inlet air. Hence, the cooling capacity of the cooling tower increases with decreasing inlet air wet bulb temperature whereas the overall water temperature fall is curtailed with increasing water to air mass ratio. The change of inlet water temperature does not affect seriously the thermal behaviour of the cooling tower. Copyright (c) 2005 John Wiley & Sons, LtdKeywords
This publication has 19 references indexed in Scilit:
- Toward to the control system of mechanical draft cooling tower of film typeInternational Journal of Heat and Mass Transfer, 2005
- Evaporative cooling of water in a mechanical draft cooling towerInternational Journal of Heat and Mass Transfer, 2003
- The Use of a Thermo-Fluid Dynamic Efficiency in Cooling TowersHeat Transfer Engineering, 2002
- Thermal behaviour of closed wet cooling towers for use with chilled ceilingsApplied Thermal Engineering, 2000
- The investigation of cooling tower packing in various arrangementsApplied Thermal Engineering, 2000
- Cooling tower—an energy conservation resourceApplied Thermal Engineering, 1999
- A general mathematical model of evaporative cooling devicesRevue Générale de Thermique, 1998
- A Modified Analysis of Counter Flow Wet Cooling TowersJournal of Heat Transfer, 1997
- An investigation into a falling film type cooling towerInternational Journal of Refrigeration, 1995
- Design of Cooling Towers by the Effectiveness-NTU MethodJournal of Heat Transfer, 1989