Investigation of the sympathetic tripping problem in power systems with large penetrations of distributed generation
Open Access
- 1 March 2015
- journal article
- research article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 9 (4), 379-385
- https://doi.org/10.1049/iet-gtd.2014.0169
Abstract
This study contains an investigation into sympathetic tripping – the undesirable disconnection of distributed generators (DGs) (in accordance with the recently-introduced G83/2 under voltage protection) when a network fault occurs in the vicinity of the DG and is not cleared quickly enough by the network protection (i.e. before the DG's under voltage protection operates). An evaluation of the severity of and proposal of solutions to the problem of sympathetic tripping on a typical UK distribution power network is presented. An inverter model (as the majority of DGs will be inverter-interfaced) that characterises the fault response of the inverter and its associated protection functions has been developed for use in simulation through exhaustive laboratory testing of a commercially-available 3 kW inverter for DG application; the observed responses have been modelled and incorporated in a power system simulation package. It is shown, when using presently-adopted DG interface and network protection settings, that the risk of sympathetic tripping is high in several future scenarios. To mitigate this risk, the impact of modifying network protection settings is evaluated. This study has two key findings – determination of the conditions at which the risk of sympathetic tripping is high and evaluation of a technique to mitigate this risk.Keywords
This publication has 10 references indexed in Scilit:
- Nondetection Index of Anti-Islanding Passive Protection of Synchronous Distributed GeneratorsIEEE Transactions on Power Delivery, 2012
- A Classification Technique for Recloser-Fuse Coordination in Distribution Systems With Distributed GenerationIEEE Transactions on Power Delivery, 2011
- IEC 61850 based smart distribution protection: Solutions for sympathetic trippingPublished by Institute of Electrical and Electronics Engineers (IEEE) ,2011
- Sympathetic trip prevention by applying simple current relaysPublished by Institute of Electrical and Electronics Engineers (IEEE) ,2010
- Understanding Fault Characteristics of Inverter-Based Distributed Energy ResourcesPublished by Office of Scientific and Technical Information (OSTI) ,2010
- A Simple Technique for Islanding Detection With Negligible Nondetection ZoneIEEE Transactions on Power Delivery, 2009
- Optimal coordination of microprocessor based directional overcurrent relays2008 Canadian Conference on Electrical and Computer Engineering, 2008
- A Modified Particle Swarm Optimizer for the Coordination of Directional Overcurrent RelaysIEEE Transactions on Power Delivery, 2007
- Modelling and Analysis of Fault Behaviour of Inverter Microgrids to Aid Future Fault DetectionPublished by Institute of Electrical and Electronics Engineers (IEEE) ,2007
- UK distribution system protection issuesIET Generation, Transmission & Distribution, 2007