Variable-Frequency Grid-Sequence Detector Based on a Quasi-Ideal Low-Pass Filter Stage and a Phase-Locked Loop
- 18 May 2010
- journal article
- Published by Institute of Electrical and Electronics Engineers (IEEE) in IEEE Transactions on Power Electronics
- Vol. 25 (10), 2552-2563
- https://doi.org/10.1109/tpel.2010.2050492
Abstract
This paper proposes a filtered-sequence phase-locked loop (FSPLL) structure for detection of the positive sequence in three-phase systems. The structure includes the use of the Park transformation and moving average filters (MAF). Performance of the MAF is mathematically analyzed and represented in Bode diagrams. The analysis allows a proper selection of the window width of the optimal filter for its application in the dq transformed variables. The proposed detector structure allows fast detection of the grid voltage positive sequence (within one grid voltage cycle). The MAF eliminates completely any oscillation multiple of the frequency for which it is designed; thus, this algorithm is not affected by the presence of imbalances or harmonics in the electrical grid. Furthermore, the PLL includes a simple-frequency detector that makes frequency adaptive the frequency depending blocks. This guarantees the proper operation of the FSPLL under large frequency changes. The performance of the entire PLL-based detector is verified through simulation and experiment. It shows very good performance under several extreme grid voltage conditions.Keywords
This publication has 41 references indexed in Scilit:
- A Generic Open-Loop Algorithm for Three-Phase Grid Voltage/Current Synchronization With Particular Reference to Phase, Frequency, and Amplitude EstimationIEEE Transactions on Power Electronics, 2009
- Comparison of Three Single-Phase PLL Algorithms for UPS ApplicationsIEEE Transactions on Industrial Electronics, 2008
- Frequency measurement in power networks in the presence of harmonics using fourier and zero crossing techniquePublished by Institute of Electrical and Electronics Engineers (IEEE) ,2005
- Frequency estimation of distorted signals for control and protection of power systemPublished by Institution of Engineering and Technology (IET) ,2004
- Comparative characteristics of main methods for dynamic estimation of frequency and magnitude parameters in power systemsPublished by Institute of Electrical and Electronics Engineers (IEEE) ,2003
- DSP methods for dynamic estimation of frequency and magnitude parameters in power system transientsPublished by Institute of Electrical and Electronics Engineers (IEEE) ,2002
- Evaluation of frequency tracking methodsIEEE Transactions on Power Delivery, 2001
- Digital filtering for robust 50/60 Hz zero-crossing detectorsIEEE Transactions on Instrumentation and Measurement, 1996
- Noise reduction in zero crossing detection by predictive digital filteringIEEE Transactions on Industrial Electronics, 1995
- Frequency tracking in power networks in the presence of harmonicsIEEE Transactions on Power Delivery, 1993