Overcurrent relays coordination considering transient behaviour of fault current limiter and distributed generation in distribution power network
- 1 January 2011
- journal article
- Published by Institution of Engineering and Technology (IET) in IET Generation, Transmission & Distribution
- Vol. 5 (9), 903-911
- https://doi.org/10.1049/iet-gtd.2010.0754
Abstract
The connecting of distributed generation (DG) to the distribution network has numerous advantages. However, in the presence of DG some problems in coordination of protection devices will occur, due to changes in short-circuit levels at different points. Fault current limiter (FCL) is applied to limit the fault current levels and the effect of DGs on coordination of overcurrent (O/C) relays during the faults. The use of DG and FCL in distribution networks causes to some transient currents during fault conditions. Steady-state coordination methods do not result in accurate settings in such networks. A new method is proposed for coordination of O/C relays by considering the transient behaviour of the network. This method is based on the genetic algorithm and uses the dynamic model of O/C relays instead of the fixed characteristic curves. For this purpose, transient behaviour of DG and FCL are simulated and the relay operating status is calculated for all primary and backup relays to achieve the optimal settings of relays in transient condition. Simulations are carried out on a sample network and the results demonstrate that the method gives feasible and effective solutions for optimal coordination in the practical power system networks in comparison to the previous steady-state methods.Keywords
This publication has 10 references indexed in Scilit:
- Optimal Relays Coordination Efficient Method in Interconnected Power SystemsJournal of Electrical Engineering, 2010
- A new comprehensive genetic algorithm method for optimal overcurrent relays coordinationElectric Power Systems Research, 2008
- Restoration of Directional Overcurrent Relay Coordination in Distributed Generation Systems Utilizing Fault Current LimiterIEEE Transactions on Power Delivery, 2008
- Time-Overcurrent Relay Coordination: A ReviewInternational Journal of Emerging Electric Power Systems, 2005
- Development of Adaptive Protection Scheme for Distribution Systems With High Penetration of Distributed GenerationIEEE Transactions on Power Delivery, 2004
- Microprocessor-based reclosing to coordinate fuse and recloser in a system with high penetration of distributed generationPublished by Institute of Electrical and Electronics Engineers (IEEE) ,2003
- A novel hybrid current-limiting circuit breaker for medium voltage: principle and test resultsIEEE Transactions on Power Delivery, 2003
- Discrete-Fourier-transform-based technique for removal of decaying DC offset from phasor estimatesIEE Proceedings - Generation, Transmission and Distribution, 2003
- Time coordination method for power system protection by evolutionary algorithmIEEE Transactions on Industry Applications, 2000
- Dispersed generation impact on distribution networksIEEE Computer Applications in Power, 1999