A Recurrent Outbreak of Nosocomial Legionnaires' Disease Detected by Urinary Antigen Testing: Evidence for Long-Term Colonization of a Hospital Plumbing System

Abstract
Background: In 1994, a hospital reported an increase in nosocomial legionnaires' disease after implementing use of a rapid urinary antigen test for Legionella pneumophila serogroup 1 (Lp-1). This hospital was the site of a previous nosocomial legionnaires' disease outbreak during 1980 to 1982. Methods: Infection control records were reviewed to compare rates of nosocomial pneumonia and the proportion of cases attributable to legionnaires' disease during the 1994 outbreak period with those during the same period in 1993. Water samples were collected for Legionella culture from the hospital's potable water system and cooling towers, and isolates were subtyped by monoclonal antibody (MAb) testing and arbitrarily primed polymerase chain reaction (AP-PCR). Results: Nosocomial pneumonia rates were similar from April through October 1993 and April through October 1994: 5.9 and 6.6 per 1,000 admissions, respectively (rate ratio [RR], 1.1; P=.56); however, 3.2% of nosocomial pneumonias were diagnosed as legionnaires' disease in 1993, compared with 23.9% in 1994 (RR, 9.4; P