Control ofLegionella pneumophila in a hospital water system by chlorine dioxide
- 1 October 1995
- journal article
- research article
- Published by Oxford University Press (OUP) in Journal of Industrial Microbiology & Biotechnology
- Vol. 15 (4), 384-390
- https://doi.org/10.1007/bf01569995
Abstract
Immuno-compromised patients are particularly susceptible to Legionnaires' Disease. After three cases of the disease occurred in a hospital, a continuous dosing regime using chlorine dioxide was initiated to replace chlorination of the water system. This study identified a number of factors which may have resulted in conditions that would encourage the growth of the water-borne pathogenLegionella pneumophila. The residual chlorination was inadequate for microbial control at the taps furthest from the four storage tanks, of which two were found to be in excess for demand. The temperature of the water in the storage tanks was also found to be above 20° C; a temperature that would encourage microbial growth. A back-up calorifier was present and was found to containL. pneumophila, and linseed oil-based sealants that provide nutrients for microbial growth were also prevalent as jointing compounds in the water circult. Although the shower heads were routinely disinfected, a requirement was identified to also disinfect the shower hoses. NoL. pneumophila were recovered from the water system after the chlorine reduced dioxide disinfection trial. Biofilm was also dramatically reduced after disinfection; however, small microcolonies were identified and proved to be metabolically active when tested with a metabolic indicator. Using light and fluorescence microscopy, the pipe samples removed from the water system were rapidly analysed for biofouling, complementing existing microbiological methods.Keywords
This publication has 11 references indexed in Scilit:
- Rapid detection of biofilm on corroded copper pipesBiofouling, 1994
- An investigation of the efficacy of a bromine containing biocide on an aquatic consortium of planktonic and biofilm micro‐organisms includingLegionella pneumophilaBiofouling, 1994
- Atomic force microscopy examination of the topography of a hydrated bacterial biofilm on a copper surfaceCurrent Microbiology, 1992
- The differential fluorescence of bacteria stained with acridine orange and the effects of heatJournal of Applied Microbiology, 1991
- The Ecology and Survival of Legionella PneumophilaWater and Environment Journal, 1989
- LEGIONELLACEAE IN THE HOSPITAL WATER-SUPPLY: Epidemiological Link with Disease and Evaluation of a Method for Control of Nosocomial Legionnaires' Disease and Pittsburgh PneumoniaThe Lancet, 1983
- LEGIONELLA PNEUMOPHILA IN WATER PLUMBING SYSTEMSThe Lancet, 1982
- EXPERIMENTAL TRANSMISSION OF LEGIONNAIRES' DISEASE BY EXPOSURE TO AEROSOLS OF LEGIONELLA PNEUMOPHILAThe Lancet, 1981
- Pittsburgh Pneumonia Agent: Direct Isolation from Human Lung TissueThe Journal of Infectious Diseases, 1980
- Direct counts of aquatic bacteria by a modified epifluorescence technique1Limnology and Oceanography, 1975