SELECTION OF SAMPLING PERIOD FOR AUTOMATIC GENERATION CONTROL

Abstract
The paper presents the analysis of automatic generation control (AGC) of a two-equal area reheat thermal system in the presence of generation rate constraints considering a discrete-continuous time mathematical model. The effect of variation of sampling period on optimum integral gain setting and system dynamic performance has been analyzed considering supplementary controllers based on conventional area control errors (ACEs) and new area control errors (ACENs). Investigations reveal that the optimum integral gain setting and system dynamic performance are hardly affected over a wide range of sampling period T for controllers based on conventional ACEs. Studies also reveal that the permissible sampling period is further enhanced with integral controllers based on new area control errors (ACENs).