Power analyzer based arduino-uno validation using Kyoritsu KEW 6315 and Hioki 328-20

Abstract
Online quality analysis technique of energy consumption is getting easier. It is because the sensor module and microprocessor are getting more simple, complex and possess high accuracy. This study offers an alternative to online electrical energy consumption monitoring technique by using Arduino. It is interesting to know the accuracy of the work of the Arduino-based energy quality monitoring system with high accuration measurments tool Kyoritsu power analyzer KEW 6315 and Hioki 328-20. The method of this research is the design of 1 phase electrical energy monitoring system by using current sensor type SCT-013 and voltage sensor in the form of transformator. EmonLib Library was used for processing voltage and current data in Arduino. The validation of measurement results was done by comparing the results of Arduino with Kyoritsu KEW 6315 and Hioki 328-20. The measurement reporting technique was displayed online based on the website. The results provide a clear picture of the measurement performance of the developed system, that the system has a quality of performance close to Kyoritsu type kew 6315 that against Hioki 328-20 with an average error below 5% is acceptable. The results of the measurement of electrical energy consumption had been successfully displayed in the form of a website-based energy report.