Research on Magnetic Field Characteristics in DC Yard of Dinghai Converter Station Under Monopolar Grounding Fault

Abstract
In Dinghai converter station of Zhoushan VSC-HVDC transmission project, 200 kV hybrid DC circuit breaker is used for the first time to realize DC side fault isolation. When DC side short circuit occurs, its fault current characteristics are different from those of AC substation and HVDC converter station, and the magnetic field interference to secondary equipment in DC yard is still unknown. In this paper, taking the single pole grounding short circuit fault with high probability in flexible DC power grid as an example, the electromagnetic transient simulation model of fault current in Dinghai converter station is established, and the time-domain current waveform is obtained. Then, the magnetic field calculation model of DC circuit breaker and other key electrical equipment is established, and the magnetic field of secondary equipment in DC yard is calculated based on Biot-Savart Law. The results show that the maximum magnetic field strength at the secondary equipment is 59 A/m, the waveform is ms level, and it is aperiodic. The distribution of magnetic field in DC yard varies between 3 and 346 A/m.

This publication has 3 references indexed in Scilit: