MINIMIZING THE EFFECT OF SATURATION OF HIGH-VOLTAGE CURRENT TRANSFORMERS ON THE ACCURACY OF THREE-PHASE PRIMARY MEASUTING CHANNELS WITH DIGITAL OUTPUT
Open Access
- 21 October 2021
- journal article
- Published by National Academy of Sciences of Ukraine (Co. LTD Ukrinformnauka) (Publications) in Tekhnichna Elektrodynamika
- Vol. 2021 (6), 58-67
- https://doi.org/10.15407/techned2021.06.058
Abstract
The classification is carried out and the characteristics, capabilities and disadvantages of the known methods of programmed correction of the output current of a single-phase primary measuring channel (PMC) of the current are determined. A discretized model of short-circuit current (SCC) is proposed. A method and an algorithm for increasing the accuracy of a three-phase current PMC in transient modes of electric power systems (EPS) under the condition of saturation of the magnetic circuits of its phase current transformers have been developed. The reliability of the developed method is confirmed by simulation of the PMC output current under the condition of phase-to-phase short-circuit of phases A and B without correction and with correction of its phase currents. It is shown that the developed method makes it possible to reduce the total error of the PMC in the transient modes of the EES under the condition of saturation of the magnetic circuits of the CT from 70-90% to 6-15%. References 47, figures 6, table 1.Keywords
This publication has 41 references indexed in Scilit:
- Correction of saturated current from measurement current transformerIET Electric Power Applications, 2013
- Busbar differential protection in conjunction with a current transformer compensating algorithmIET Generation, Transmission & Distribution, 2008
- Detection and correction of distorted current transformer current using wavelet transform and artificial intelligenceIET Generation, Transmission & Distribution, 2008
- A Series Multiresolution Morphological Gradient-Based Criterion to Identify CT SaturationIEEE Transactions on Power Delivery, 2006
- Compensating algorithm suitable for use with measurement-type current transformers for protectionIEE Proceedings - Generation, Transmission and Distribution, 2005
- An Efficient Compensation Algorithm for Current Transformer Saturation EffectsIEEE Transactions on Power Delivery, 2004
- Compensation of the Distortion in the Secondary Current Caused by Saturation and Remanence in a CTIEEE Transactions on Power Delivery, 2004
- Electronic system for increasing the accuracy of in-service instrument-current transformersIEEE Transactions on Instrumentation and Measurement, 2003
- Compensation of nonlinearities in a current transformer for the reconstruction of the primary currentIEEE Transactions on Control Systems Technology, 2001
- An algorithm for compensating secondary currents of current transformersIEEE Transactions on Power Delivery, 1997