Detection of Ferroresonance Oscillations in Medium Voltage Networks
Open Access
- 10 August 2020
- Vol. 13 (16), 4129
- https://doi.org/10.3390/en13164129
Abstract
This paper presents a new algorithm for the detection of ferroresonance oscillations in medium voltage (MV) power systems. The proposed method is based on an analysis of estimated flux resulting from the voltage in open delta voltage transformer (VT) connection. The testing results proved that the new solution is capable of identifying quickly and reliably ferroresonance oscillations and it does not maloperate during faults. In addition, this method is simple for hardware implementation. The developed solution has been thoroughly tested on simulation runs (from the MATLAB2019b/Simulink program), as well as recorded signals.This publication has 7 references indexed in Scilit:
- Detection of ferroresonance occurrence in inductive voltage transformers through vibration analysisInternational Journal of Electrical Power & Energy Systems, 2018
- Identification of ferroresonance based on S-transform and support vector machineSimulation Modelling Practice and Theory, 2010
- On the Use of Wavelet Decomposition for Ferroresonance Detection in Power SystemPublished by Institute of Electrical and Electronics Engineers (IEEE) ,2009
- Mitigating Ferroresonance in Voltage Transformers in Ungrounded MV NetworksIEEE Transactions on Power Delivery, 2007
- Characterization of ferroresonant modes in HV substation with CB grading capacitorsElectric Power Systems Research, 2007
- Modeling and analysis guidelines for slow transients. III. The study of ferroresonanceIEEE Transactions on Power Delivery, 2000
- Voltage transformer ferroresonance in 275 kV substationPublished by Institution of Engineering and Technology (IET) ,1999