The research to reduce the transient grounding resistance of communication protection system with resistance matching method

Abstract
In this paper, we study reducing the transient grounding resistance (TGR) of communication protection system with resistance matching method. We set single or double matching layers surround the grounding rod and change their sizes and conductivity to get the laws about reducing the TGR peak and stable value. The finite-difference time-domain (FDTD) method is adopted for calculating. For the single matching layer, both of the peak and stable value of the vertical grounding rod TGR reduce, compared with normal case, as matching layer exists when the conductivity of matching layer is larger than that of ground. For the double matching layers, the TGR value will reduce even more than single matching layer case when the conductivity of outer matching layer is larger than that of ground.